Zoom In
Zoom Out
Enlarge
*Product images are for illustrative purposes only and may differ from the actual product.
Thermocouple - 105°C Single Pair - Overall Shield
Armored
PVC Jacket & Insulation
Single Pair
Overall Shield
105°C
Construction |
Category Conductor Description |
16AWG solid thermocouple wire
|
Category Insulation Description |
Flame-retardant 105°C Polyvinyl Chloride (PVC)
Color-coded per ANSI
|
Pair Assembly |
Insulated
|
Shield |
Polyester backed aluminum tape
7 strand tinned copper drain wire
|
Inner Jacket |
Black, 105°C Flame-Retardant Polyvinyl Chloride (PVC)
|
Armor |
Continuously welded, corrugated aluminum alloy sheath per UL 1569
|
Overall Jacket |
105°C Flame-retardant Polyvinyl Chloride (PVC)
Color-coded per ANSI
|
-
Armored Thermocouple Extension cables provide superior protection and reliability against physical damage for use in instrumentation and process control applications requiring ITC-HL or PLTC wiring methods
-
Recognized for use in Class I, Division 2; Class II, Division 2; Class III, Division 2 or Class I, Zone 2 hazardous locations per NEC Articles 501, 502, 503, and 505
-
Installed indoors or outdoors, in wet or dry locations, in a raceway, as aerial cable on a messenger, in cable trays, or for direct burial
-
Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute
-
UL 13 Power-Limited Circuit Cables
-
UL 2250 Instrumentation Tray Cable
-
UL 1569 Metal Clad Cables
-
UL 1309/CSA C22.2 No. 245 Marine Shipboard Cable
-
UL Type PLTC, SUN RES, DIR BUR, -40°C
-
UL Listed Marine Shipboard
Part Number Table
Part # |
Gauge |
Pairs |
Thermocouple Type |
Jacket Color |
Nominal OD over Core |
Nominal OD over Armor |
Nominal OD Overall |
Material Weight (Lbs./M') |
XI11602-EX |
16 |
1 |
E Extension grade |
Purple |
.250 |
.450 |
.560 |
132 |
XI11602-JX |
16 |
1 |
J Extension grade |
Black |
.250 |
.450 |
.560 |
132 |
XI11602-KX |
16 |
1 |
K Extension grade |
Yellow |
.250 |
.450 |
.560 |
132 |
XI11602-TX |
16 |
1 |
T Extension grade |
Blue |
.250 |
.450 |
.560 |
132 |
Note: The data shown is approximate and subject to standard industry and manufacturer tolerances