Construction
Category Conductor Description Bare annealed copper per ASTM B3 Compact stranding per ASTM B496
Extruded Strand Shield Extruded thermoset semi-conductor stress control layer over conductor per ICEA S-96-659 and UL 1072
Category Insulation Description 90 mils Ethylene Propylene Rubber (EPR) per ICEA S-96-659 and UL 1072 Insulation is printed 1-Black, 2-Red, and 3-Blue for phase identification
Grounding Conductor Three split Class B stranded bare annealed copper grounding conductors Sized in accordance with UL 1072 and NEC Table 250.122
Armor Continuous, impervious, welded, corrugated aluminum armor
Category Jacket Description Flame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC), yellow Low temperature performance meets ASTM D746 brittleness temperature at or below 40°C
  • Variable Frequency Drives: 3-conductor CCW armored cables with 3 symmetrical grounding wire are the preferred wiring method for use with AC motors controlled by pulse-width modulated inverters in VFD applications
  • For use in feeders and branch circuits in industrial power distribution systems per NEC articles 328 and 330
  • Approved for Classes I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2, hazardous locations covered under NEC Articles 501, 502, and 503
  • Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced no more than 6 feet apart
  • Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Conductors Ground Gauge Insulation Thickness Nominal OD over Armor Nominal OD Overall Material Weight (Lbs./M')
XMVE10403 4 3 3 x #10 0.09 1.19 1.30 965
XMVE10203 2 3 3 x #10 0.09 1.34 1.45 1333
XMVE11/003 1/0 3 3 x #8 0.09 1.51 1.65 1880
XMVE12/003 2/0 3 3 x #8 0.09 1.60 1.73 2204
XMVE14/003 4/0 3 3 x #7 0.09 1.83 1.96 3184
XMVE125003 250 3 3 x #7 0.09 1.96 2.09 3582
XMVE135003 350 3 3 x #6 0.09 2.19 2.32 4836
XMVE150003 500 3 3 x #5 0.09 2.45 2.61 6491
XMVE175003 750 3 3 x #4 0.09 2.93 3.10 9463