ALUSE-2-6 Aluminum, XLPE Insulated 600V90°C Dry, Wet, Direct Burial

*Product images are for illustrative purposes only and may differ from the actual product.

ALUSE-2-6 Aluminum, XLPE Insulated 600V90°C Dry, Wet, Direct Burial

Part #: ALUSE-2-6

Please select all above options before adding to cart.
Construction
Category Conductor Description Compact stranded AA-8000 series aluminum alloy per ASTM B801 or ASTM B836 and ASTM B801
Category Insulation Description Black, thermoset cross-linked polyethylene (XLPE) meeting the requirements of RHH/RHW-2/USE-2 per UL 44 and UL 855
Category Standards "• UL 44 • UL 854 • NEMA WC 70/ICEA S-95-658 • Requirements of the National Electrical Code • ASTM B800, B801, B836 • Sunlight resistant • Oil Resistant PRI/PRII • Gas and Oil Res GRI/GRII • RUS ACCEPTED"
Applications The cable is rated at 600 volts and 90 ̊C for use in wet, dry, and direct burial. RHH/ RHW-2/USE-2 can be used in conduit, raceway, aerially (when supported) and directly buried in earth as recognized by the NEC.
  • "• UL 44 • UL 854 • NEMA WC 70/ICEA S-95-658 • Requirements of the National Electrical Code • ASTM B800, B801, B836 • Sunlight resistant • Oil Resistant PRI/PRII • Gas and Oil Res GRI/GRII • RUS ACCEPTED"

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Insulation Thickness Outside Diameter Inches
ALUSE-2-6 6 60 0.29
ALUSE-2-4 4 60 0.34
ALUSE-2-2 2 60 0.39
ALUSE-2-1 1 80 0.46
ALUSE-2-1/0 1/0 80 0.5
ALUSE-2-2/0 2/0 80 0.54
ALUSE-2-3/0 3/0 80 0.59
ALUSE-2-4/0 4/0 80 0.64
ALUSE-2-250 250 95 0.71
ALUSE-2-350 350 95 0.81
ALUSE-2-500 500 95 0.93
ALUSE-2-600 600 110 1.04
ALUSE-2-750 750 110 1.13