Zoom In
Zoom Out
Enlarge
*Product images are for illustrative purposes only and may differ from the actual product.
CCW Armored Composite Power and Control
Continuously Corrugated Welded Cable - CCW®
Composite Power & Control
XLPE Insulation - PVC Jacket
90°C - 600 Volt - UL Type MC-HL
Construction |
Category Conductor Description |
Bare, annealed copper conforming to ASTM B-3
10AWG and smaller are Class B compressed stranding per ASTM B8
8AWG and larger are compact stranding per ASTM B496
|
Category Insulation Description |
Cross-linked Polyethylene (XLPE) type XHHW per UL 44, listed XHHW-2
|
Grounding Conductor |
Class B stranded bare annealed copper per ASTM B3 and B8
|
CCW Armor |
Impervious, continuously welded and corrugated aluminum alloy sheath
|
Category Jacket Description |
Black, flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)
|
-
For use as services, feeders and branch circuits for power, lighting, control, and signal circuits in accordance with NEC articles 330 and 725
-
Class I, II and III, Divisions 1 and 2; Class I, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503, and 505
-
Installed indoors or outdoors, wet or dry locations, direct buried, embedded in concrete, in a raceway, as aerial on a messenger, or as exposed runs secured to supports in accordance with NEC article 330
-
Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute
-
UL Type MC-HL, XHHW-2
-
UL listed Marine Shipboard
-
UL 44, 1309, 1569, 1581, and 2225
-
IEEE 1202 available upon request
Part Number Table
Part # |
Power Conductor AWG |
Control Conductor AWG |
Ground Gauge |
Nominal OD over Armor |
Nominal OD Overall |
Material Weight (Lbs./M') |
XAC31003 |
3 x 10AWG |
4 x #12AWG |
10 |
.750 |
.860 |
430 |
XAC30803 |
3 x 8AWG |
4 x #12AWG |
10 |
.890 |
.990 |
535 |
XAC30603 |
3 x 6AWG |
4 x #12AWG |
8 |
.930 |
1.03 |
660 |
XAC30403 |
3 x 4AWG |
4 x #12AWG |
8 |
.970 |
1.08 |
815 |
4AWG and larger uses Black with printed numbers
Note: The information in this specification sheet is approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager
General Cable CCW® is a registered trademark of General Cable