CCW Instrumentation - Ind. & Overall Shield - 105°C
Continuously Corrugated Welded Cable - CCW®
PVC/Nylon Insulation - PVC Jackets
Pairs & Triads - Individual & Overall Shields
105°C - 300 Volt - UL Type ITC-HL/PLTC
Construction |
Category Conductor Description |
Bare, annealed copper conforming to ASTM B-3 and stranded in accordance with ASTM B8 (Class B)
|
Category Insulation Description |
Flame-retardant Polyvinyl Chloride (PVC) and nylon covering, rated 105°C per UL Standard 13 & 2250
Color Code: ICEA Method 1
|
Individual Shield |
Aluminum/polyester tape with 100% coverage
Drain wire
|
Overall Shield |
Aluminum/polyester tape shield providing 100% coverage
Drain wire
|
Inner Jacket |
Flame-retardant Polyvinyl Chloride (PVC) per UL Standards 13 and 2250
Low temperature performance meets ASTM D746 brittleness temperature at or below 40°C
Nylon rip cord to facilitate jacket removal
|
Armor |
Impervious, continuously corrugated and welded aluminum per UL 1569
Meets grounding requirements of NEC Article 250
|
Overall Jacket |
Flame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC) per UL Standards 13 and 2250
Low temperature performance meets ASTM D746 brittleness temperature at or below -40°C
|
-
For use as Power Limited Tray Cable on circuits rated 150V or less and 5 amps or less in Class 2 or Class 3 circuits in accordance with NEC Article 725
-
For use as instrumentation tray cable on circuits rated 150V or less and 5 amps or less in accordance with NEC article 727
-
Recognized for use in Class I, II, and III, Divisions 1 and 2; or Class 1, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503 and 505
-
Installed indoors and outdoors, in wet or dry locations, in a raceway, as aerial cable on a messenger, in cable trays, or for direct burial
-
Recognized for use on fixed or floating offshore petroleum facilities as recommended by American Petroleum Institute
-
UL Type PLTC and ITC-HL
-
UL 13, 2250, 1569, 1309, and 1581
-
IEEE 1202 available upon request
Part Number Table
Part # |
Gauge |
Pairs |
Triads |
Nominal OD over Core |
Nominal OD over Armor |
Nominal OD Overall |
Material Weight (Lbs./M') |
XL31602 |
16 |
2 |
- |
.440 |
.670 |
.780 |
268 |
XL31604 |
16 |
4 |
- |
.520 |
.710 |
.820 |
403 |
XL31608 |
16 |
8 |
- |
.690 |
.930 |
1.04 |
528 |
XL31612 |
16 |
12 |
- |
.810 |
1.06 |
1.17 |
783 |
XL31624 |
16 |
24 |
- |
1.10 |
1.37 |
1.48 |
1628 |
XL61604 |
16 |
- |
4 |
.580 |
.800 |
.910 |
378 |
XL61608 |
16 |
- |
8 |
.790 |
1.02 |
1.13 |
621 |
XL61612 |
16 |
- |
12 |
.950 |
1.19 |
1.30 |
879 |
Note: The information in this specification sheet is approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager