HW170: LifeGuard™-TRAY CABLE - POWER CABLE 600 Volt UL Type TC-LS, 90°C XLP XHHW-2 Insulation Low Smoke Zero Halogen

*Product images are for illustrative purposes only and may differ from the actual product.

HW170: LifeGuard™-TRAY CABLE - POWER CABLE 600 Volt UL Type TC-LS, 90°C XLP XHHW-2 Insulation Low Smoke Zero Halogen


Please select all above options before adding to cart.
Construction
Category Conductor Description Tin coated soft annealed copper per ASTM B-33, Class B stranding per ASTM B-8
Category Jacket Description Sunlight-resistant and flame-retardant, Low Smoke Zero Halogen polyolefin per UL Standard 1277. A ripcord is applied longitudinally under the jacket to facilitate stripping
Category Insulation Description Cross-linked polyethylene (XLP) per UL Standard 44 for Type XHHW-2 conductors
Category Features Tray rated Sunlight-resistant Approved for direct burial Tinned conductors provide ease of termination and added protection in caustic environments Very low smoke production when burned
Category Applications LifeGuard™ jacket is highly flame retardant, produces very small amounts of smoke when burned and contains no halogens. LifeGuard™ cable is ideal for applications where a high degree ofsafety and equipment protection is required. LifeGuard™ cable is UL listed as Type TC-LS and approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays and direct burial in circuits not exceeding 600 volts. It may be installed in temperatures as low as -30°C and used in NEC Class I, Division 2 hazardous locations. It is UL approved for continuous operation at 90°C in wet and dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Exposed Run (ER) rating available upon reques
  • LifeGuard™ jacket is highly flame retardant, produces very small amounts of smoke when burned and contains no halogens. LifeGuard™ cable is ideal for applications where a high degree ofsafety and equipment protection is required. LifeGuard™ cable is UL listed as Type TC-LS and approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays and direct burial in circuits not exceeding 600 volts. It may be installed in temperatures as low as -30°C and used in NEC Class I, Division 2 hazardous locations. It is UL approved for continuous operation at 90°C in wet and dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Exposed Run (ER) rating available upon reques

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Conductors Stranding Insulation Thickness Jacket Thickness Outside Diameter Inches Weight
HW17001002 10 2 7 30 45 0.45 119.000
HW17001003 10 3 7 30 45 0.48 162.000
HW17001004 10 4 7 30 60 0.52 207.000
HW17001005 10 5 7 30 60 0.58 272.000
HW17001007 10 7 7 30 60 0.65 358.000
HW17001009 10 9 7 30 60 0.77 459.000
HW17001012 10 12 7 30 60 0.91 628.000
HW17001019 10 19 7 30 60 1.05 935.000
HW17001202 12 2 7 30 45 0.4 87.000
HW17001203 12 3 7 30 45 0.42 117.000
HW17001204 12 4 7 30 45 0.46 147.000
HW17001205 12 5 7 30 60 0.5 178.000
HW17001207 12 7 7 30 60 0.58 253.000
HW17001209 12 9 7 30 60 0.68 360.000
HW17001212 12 12 7 30 60 0.76 409.000
HW17001219 12 19 7 30 60 0.93 651.000
HW17001225 12 25 7 30 60 1.01 894.000
HW17001230 12 30 7 30 60 1.18 1040.000
HW17001237 12 37 7 30 60 1.27 1256.000
HW17001402 14 2 7 30 45 0.36 66.000
HW17001403 14 3 7 30 45 0.38 86.000
HW17001404 14 4 7 30 45 0.42 108.000
HW17001405 14 5 7 30 45 0.45 130.000
HW17001407 14 7 7 30 60 0.49 169.000
HW17001409 14 9 7 30 60 0.62 238.000
HW17001412 14 12 7 30 60 0.69 298.000
HW17001419 14 19 7 30 60 0.8 438.000
HW17001425 14 25 7 30 60 0.96 631.000
HW17001430 14 30 7 30 60 1.04 721.000
HW17001437 14 37 7 30 60 1.13 867.000