Zoom In
Zoom Out
Enlarge
*Product images are for illustrative purposes only and may differ from the actual product.
5/8kV - CCW Armored Power, Shielded, 3/C VFD
Part #: XMVE24/003
Continuously Corrugated Welded Cable – CCW®
Variable Frequency Drive Cable
EPR Insulation - PVC Jacket
105°C - UL Type MC-HL or MV-105
5kV(133%)/8kV(100%) - 3-Conductor - Shielded
Related Products
Construction |
Category Conductor Description |
Bare annealed copper per ASTM B3
Compact stranding per ASTM B496
|
Extruded Strand Shield |
Extruded thermoset semi-conductor stress control layer over conductor per ICEA S-93-639 and UL 1072
|
Category Insulation Description |
Ethylene Propylene Rubber (EPR)
|
Grounding Conductor |
Three split Class B stranded bare annealed copper grounding conductors
Sized in accordance with UL 1072 and NEC Article 250
|
Armor |
Impervious, continuously welded and corrugated aluminum alloy sheath
|
Category Jacket Description |
Flame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC), yellow
Low temperature performance meets ASTM D746 brittleness temperature at or below 40°C
|
-
Variable Frequency Drives: 3-conductor CCW armored cables with 3 symmetrical grounding wire are the preferred wiring method for use with AC motors controlled by pulse-width modulated inverters in VFD applications
-
For use in feeders and branch circuits in industrial power distribution systems per NEC articles 328 and 330
-
Approved for Classes I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2, hazardous locations covered under NEC Articles 501, 502, 503 and 505 Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced no more than 6 feet apart
-
Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete
-
UL 1072
-
UL 1569
-
UL 2225
-
UL 1309
-
IEEE 1202 available upon request
Part Number Table
Part # |
Gauge |
Conductors |
Ground Gauge |
Insulation Thickness |
Nominal OD over Armor |
Nominal OD Overall |
Material Weight (Lbs./M') |
XMVE20603 |
6 |
3 |
3 x 10AWG |
0.115 |
1.37 |
1.48 |
1121 |
XMVE20403 |
4 |
3 |
3 x 10AWG |
0.115 |
1.51 |
1.65 |
1418 |
XMVE20203 |
2 |
3 |
3 x 10AWG |
0.115 |
1.64 |
1.78 |
1764 |
XMVE21/003 |
1/0 |
3 |
3 x 8AWG |
0.115 |
1.78 |
1.91 |
2314 |
XMVE22/003 |
2/0 |
3 |
3 x 8AWG |
0.115 |
1.92 |
2.05 |
2671 |
XMVE24/003 |
4/0 |
3 |
3 x 7AWG |
0.115 |
2.15 |
2.28 |
3727 |
XMVE225003 |
250 |
3 |
3 x 6AWG |
0.115 |
2.23 |
2.36 |
4060 |
XMVE235003 |
350 |
3 |
3 x 6AWG |
0.115 |
2.45 |
2.61 |
5264 |
XMVE250003 |
500 |
3 |
3 x 5AWG |
0.115 |
2.75 |
2.92 |
7250 |
XMVE275003 |
750 |
3 |
3 x 4AWG |
0.115 |
3.32 |
3.50 |
10505 |
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager
General Cable CCW® is a registered trademark of General Cable